Reference tables

2023 NEC

Conduit Fill Capacity Tables

Permitted fill percentages, conduit internal areas for EMT, PVC Schedule 40, and RMC, and conductor cross-sectional areas by insulation type.

NEC 2023Every value in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Permitted fill

One conductor53%
Two conductors31%
More than two conductors40%

Conduit internal area (in²)

Total internal cross-sectional area of each conduit type by trade size.
Trade sizeEMTPVC Sch 40RMC
1/2"0.3040.2850.314
3/4"0.5330.5080.549
1"0.8640.8320.887
1-1/4"1.4961.4531.526
1-1/2"2.0361.9862.071
2"3.3563.2913.408
2-1/2"5.8584.6954.866
3"8.8467.2687.499
3-1/2"11.5459.73710.01
4"14.75312.55412.882

Conductor area (in²)

Approximate cross-sectional area of each insulated conductor, including insulation. A dash means the published table does not list that insulation at that size.
SizeTHHN / THWN-2XHHW-2THW
14 AWG0.00970.01390.0209
12 AWG0.01330.01810.026
10 AWG0.02110.02430.0333
8 AWG0.03660.04370.0556
6 AWG0.05070.0590.0726
4 AWG0.08240.08140.0973
3 AWG0.09730.09620.1134
2 AWG0.11580.11460.1333
1 AWG0.15620.15340.1901
1/0 AWG0.18550.18250.2223
2/0 AWG0.22230.2190.2624
3/0 AWG0.26790.26420.3117
4/0 AWG0.32370.31970.3718
250 kcmil0.3970.39040.4596
300 kcmil0.46080.45360.5281
350 kcmil0.52420.51660.5958
400 kcmil0.58630.57820.6619
500 kcmil0.70730.69840.7901
600 kcmil0.86760.87090.9729
700 kcmil0.98870.99231.101
750 kcmil1.04961.05321.1652
800 kcmil1.10851.11221.2272
900 kcmil1.23111.23511.3561
1000 kcmil1.34781.35191.4784
1250 kcmil-1.7181.8602
1500 kcmil-2.01562.1695
1750 kcmil-2.31272.4773
2000 kcmil-2.60732.7818

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).

Why two conductors get a lower limit than three

It looks like a typo but it isn't. Exactly two conductors in a round pipe can wedge against the wall on a bend - the jam ratio problem - while three or more bundle together and roll through. The tighter limit for two is a mechanical allowance, not a thermal one.

Fill and derating are the same problem

Both exist because bundled conductors cannot shed heat. Filling a conduit to the limit with current-carrying conductors will also trigger the bundling adjustment, reducing what each one carries. Passing the fill check does not mean the ampacity is unaffected.

Build a specific set in the conduit fill calculator, which handles mixed conductor sizes.

Related

Other tables