3-1/2" EMT has an internal area of 11.545 in². At the 40% limit that applies to more than two conductors, it holds up to 347 12 AWG THHN conductors.
Capacity
Maximum conductors by size and insulation
NEC 2023Every count in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
Maximum number of same-size, same-insulation conductors in 3-1/2" EMT (11.545 in² internal). Counts above two use the 40% limit; a dash means not even one fits, or the published area table does not list that insulation at that size.
Conductor
THHN / THWN-2
XHHW-2
THW
14 AWG
400
332
220
12 AWG
347
255
177
10 AWG
218
190
138
8 AWG
126
105
83
6 AWG
91
78
63
4 AWG
56
56
47
3 AWG
47
48
40
2 AWG
39
40
34
1 AWG
29
30
24
1/0 AWG
24
25
20
2/0 AWG
20
21
17
3/0 AWG
17
17
14
4/0 AWG
14
14
12
250 kcmil
11
11
10
300 kcmil
10
10
8
350 kcmil
8
8
7
400 kcmil
7
7
6
500 kcmil
6
6
5
600 kcmil
5
5
4
700 kcmil
4
4
4
750 kcmil
4
4
3
800 kcmil
4
4
3
900 kcmil
3
3
3
1000 kcmil
3
3
3
1250 kcmil
-
2
1
1500 kcmil
-
1
1
1750 kcmil
-
1
1
2000 kcmil
-
1
1
Fill limits
NEC 2023Every area and limit below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
Internal area
11.545 in²
One conductor
53% - 6.1189 in²
Two conductors
31% - 3.5789 in²
More than two
40% - 4.6180 in²
Fitting is not the same as finishing
These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.
Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count - the conduit fill calculator handles that.
Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry - see the bundling adjustment table.
Source:NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).