4" EMT has an internal area of 14.753 in². At the 40% limit that applies to more than two conductors, it holds up to 400 12 AWG THHN conductors.
Capacity
Maximum conductors by size and insulation
NEC 2023Every count in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
Maximum number of same-size, same-insulation conductors in 4" EMT (14.753 in² internal). Counts above two use the 40% limit; a dash means not even one fits, or the published area table does not list that insulation at that size.
Conductor
THHN / THWN-2
XHHW-2
THW
14 AWG
400
400
282
12 AWG
400
326
226
10 AWG
279
242
177
8 AWG
161
135
106
6 AWG
116
100
81
4 AWG
71
72
60
3 AWG
60
61
52
2 AWG
50
51
44
1 AWG
37
38
31
1/0 AWG
31
32
26
2/0 AWG
26
26
22
3/0 AWG
22
22
18
4/0 AWG
18
18
15
250 kcmil
14
15
12
300 kcmil
12
13
11
350 kcmil
11
11
9
400 kcmil
10
10
8
500 kcmil
8
8
7
600 kcmil
6
6
6
700 kcmil
5
5
5
750 kcmil
5
5
5
800 kcmil
5
5
4
900 kcmil
4
4
4
1000 kcmil
4
4
3
1250 kcmil
-
3
3
1500 kcmil
-
2
2
1750 kcmil
-
1
1
2000 kcmil
-
1
1
Fill limits
NEC 2023Every area and limit below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
Internal area
14.753 in²
One conductor
53% - 7.8191 in²
Two conductors
31% - 4.5734 in²
More than two
40% - 5.9012 in²
Fitting is not the same as finishing
These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.
Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count - the conduit fill calculator handles that.
Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry - see the bundling adjustment table.
Source:NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).