2023 NEC · 324 worked scenarios

Wire size by load and distance.

Pick the load and the run length and read the answer. Every page below sizes the conductor for ampacity and for a 3% voltage drop over the distance, in copper and aluminum, and says which of the two governs. If your conditions differ, the calculator takes them all.

324
Load and distance combinations
18
Load currents, 15 A to 200 A
12
Run lengths, 25 ft to 400 ft
81
Long runs where drop usually governs

NEC 2023Every scenario linked below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

120 V single phase

120 V branch circuits

15 A

20 A

25 A

30 A

35 A

40 A

45 A

50 A

60 A

240 V single phase

240 V circuits, feeders, and subpanels

15 A

20 A

25 A

30 A

35 A

40 A

45 A

50 A

60 A

70 A

80 A

90 A

100 A

110 A

125 A

150 A

175 A

200 A

Long runs

Where voltage drop takes over

Past roughly 300 feet, ampacity usually stops being the binding requirement. The conductor that safely carries the current will still deliver too little voltage at the far end, so the size goes up on performance grounds - a detached shop, a well pump, a barn, an EV charger at the end of a long driveway. Voltage-drop limits are recommendations in the 2023 NEC rather than requirements, though specifications and some jurisdictions enforce them. For what the figure means and why 120 V runs suffer twice as badly, read what voltage drop is and when it matters.

15 A · 300 ft · 120 V15 A · 350 ft · 120 V15 A · 400 ft · 120 V20 A · 300 ft · 120 V20 A · 350 ft · 120 V20 A · 400 ft · 120 V25 A · 300 ft · 120 V25 A · 350 ft · 120 V25 A · 400 ft · 120 V30 A · 300 ft · 120 V30 A · 350 ft · 120 V30 A · 400 ft · 120 V35 A · 300 ft · 120 V35 A · 350 ft · 120 V35 A · 400 ft · 120 V40 A · 300 ft · 120 V40 A · 350 ft · 120 V40 A · 400 ft · 120 V45 A · 300 ft · 120 V45 A · 350 ft · 120 V45 A · 400 ft · 120 V50 A · 300 ft · 120 V50 A · 350 ft · 120 V50 A · 400 ft · 120 V60 A · 300 ft · 120 V60 A · 350 ft · 120 V60 A · 400 ft · 120 V15 A · 300 ft · 240 V15 A · 350 ft · 240 V15 A · 400 ft · 240 V20 A · 300 ft · 240 V20 A · 350 ft · 240 V20 A · 400 ft · 240 V25 A · 300 ft · 240 V25 A · 350 ft · 240 V25 A · 400 ft · 240 V30 A · 300 ft · 240 V30 A · 350 ft · 240 V30 A · 400 ft · 240 V35 A · 300 ft · 240 V35 A · 350 ft · 240 V35 A · 400 ft · 240 V40 A · 300 ft · 240 V40 A · 350 ft · 240 V40 A · 400 ft · 240 V45 A · 300 ft · 240 V45 A · 350 ft · 240 V45 A · 400 ft · 240 V50 A · 300 ft · 240 V50 A · 350 ft · 240 V50 A · 400 ft · 240 V60 A · 300 ft · 240 V60 A · 350 ft · 240 V60 A · 400 ft · 240 V70 A · 300 ft · 240 V70 A · 350 ft · 240 V70 A · 400 ft · 240 V80 A · 300 ft · 240 V80 A · 350 ft · 240 V80 A · 400 ft · 240 V90 A · 300 ft · 240 V90 A · 350 ft · 240 V90 A · 400 ft · 240 V100 A · 300 ft · 240 V100 A · 350 ft · 240 V100 A · 400 ft · 240 V110 A · 300 ft · 240 V110 A · 350 ft · 240 V110 A · 400 ft · 240 V125 A · 300 ft · 240 V125 A · 350 ft · 240 V125 A · 400 ft · 240 V150 A · 300 ft · 240 V150 A · 350 ft · 240 V150 A · 400 ft · 240 V175 A · 300 ft · 240 V175 A · 350 ft · 240 V175 A · 400 ft · 240 V200 A · 300 ft · 240 V200 A · 350 ft · 240 V200 A · 400 ft · 240 V