Reference tables

2023 NEC

Conductor Bundling Adjustment Factors

Adjustment factors applied when more than three current-carrying conductors share a raceway or cable.

NEC 2023Every value in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Adjustment applied when more than three current-carrying conductors are bundled together or run in the same raceway for more than 24 inches.
Current-carrying conductorsPercent of table ampacityMultiplier
1-3100%1.00
4-680%0.80
7-970%0.70
10-2050%0.50
21-3045%0.45
31-4040%0.40
41 and above35%0.35

Source: NFPA 70, National Electrical Code, Table 310.15(C)(1). Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).

What counts as current-carrying

This is the part people get wrong. Equipment grounding conductors do not count. Neutral conductors that carry only the unbalanced current of a normal balanced multiwire circuit generally do not count either - but a neutral on a circuit feeding substantial nonlinear load does count, because harmonic currents put real load on it.

The count is also per raceway, and only applies where the bundle runs more than 24 inches. Short nipples between enclosures do not trigger it.

Why bundling matters

Each conductor in a bundle is a heat source, and the ones in the middle have nowhere to shed it. Nine conductors in a pipe heat each other to the point that each carries only half its table value. This is also why conduit fill is limited: fill and derating are two expressions of the same thermal problem.

Combine this with the temperature correction - a hot attic full of conductors gets both, multiplied, and the result can be startling.