Aluminum Conductor Ampacity Table

Allowable ampacity of aluminum and copper-clad aluminum conductors from 12 AWG to 2000 kcmil at 60°C, 75°C, and 90°C.

NEC 2023Every value in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Allowable ampacity of insulated aluminum conductors rated up to 2000 V, with not more than three current-carrying conductors in a raceway, cable, or earth, based on an ambient temperature of 30°C (86°F). The final column is the separate small-conductor overcurrent ceiling, which applies regardless of the ampacity shown.
Size60°C75°C90°COvercurrent cap
12 AWG15202515 A
10 AWG25303525 A
8 AWG354045-
6 AWG405055-
4 AWG556575-
3 AWG657585-
2 AWG7590100-
1 AWG85100115-
1/0 AWG100120135-
2/0 AWG115135150-
3/0 AWG130155175-
4/0 AWG150180205-
250 kcmil170205230-
300 kcmil195230260-
350 kcmil210250280-
400 kcmil225270305-
500 kcmil260310350-
600 kcmil285340385-
700 kcmil315375425-
750 kcmil320385435-
800 kcmil330395445-
900 kcmil355425480-
1000 kcmil375445500-
1250 kcmil405485545-
1500 kcmil435520585-
1750 kcmil455545615-
2000 kcmil470560630-

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, 240.4(D). Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).

Reading this table

The three temperature columns are the conductor's insulation rating, not the ambient temperature. A 90°C-rated conductor is not permitted to run hotter than the equipment it terminates on allows - and most breakers and equipment are listed for 60°C or 75°C. In practice the 75°C column governs most installations, and the 90°C column is used as the starting point for derating rather than as a final ampacity.

The overcurrent cap column

The smallest conductors carry a fixed protection ceiling that is separate from ampacity. It exists because small conductors have little thermal mass and are easily damaged, and it applies regardless of what the temperature columns read. The cited section carries specific exceptions this table does not reproduce.

Aluminum specifics

Aluminum is not listed at 14 AWG. Compared with copper of the same size it carries less current and has higher resistance, so aluminum runs need larger conductors and drop more voltage over the same distance. It also requires terminations listed for aluminum and an antioxidant compound at connections - the corrosion and creep failures aluminum is remembered for are largely termination failures.

Before you use these numbers

Correct for ambient temperature and adjust for the number of current-carrying conductors before sizing anything - see the temperature correction and bundling adjustment tables, or let the ampacity lookup apply both.

Related

Other tables

FAQ

Frequently asked questions

Which temperature column should I use?

The three temperature columns are the conductor's insulation rating, not the ambient temperature, and a conductor is not permitted to run hotter than the equipment it terminates on allows. Most breakers and equipment are listed for 60°C or 75°C, so in practice the 75°C column governs most installations and the 90°C column is used as the starting point for derating rather than as a final ampacity.

Does the 80 percent rule apply to these ampacities?

Not to the table values themselves - they are allowable ampacities at a 30°C ambient with no more than three current-carrying conductors. Continuous loading is handled separately: a load that runs three hours or more is sized at 125 percent, which is the same arithmetic as loading the circuit to 80 percent. The smallest conductors also carry a fixed overcurrent cap that applies regardless of what the temperature columns read.

When does aluminum need upsizing?

Compared with copper of the same size, aluminum carries less current and has higher resistance, so aluminum runs need larger conductors and drop more voltage over the same distance. Aluminum is not listed at 14 AWG, and it requires terminations listed for aluminum plus an antioxidant compound at connections.