Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

250 kcmil aluminum wire ampacity

At a 75°C termination rating, 250 kcmil aluminum carries 205 A under the published table's basis conditions - 30°C ambient, no more than three current-carrying conductors.

250 kcmil250,000 cmil

NEC 2023Every ampacity below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Ampacity by temperature rating

250 kcmil aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.
Temperature ratingAmpacityTypical insulation
60°C170 A-
75°C205 ATHW
90°C230 ATHHN / THWN-2, XHHW-2

What 250 kcmil aluminum is used for

250 kcmil aluminum carries 205 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 200 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 205 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

NEC 2023Every derated value in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

250 kcmil aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4-6 → 80%, 7-9 → 70%, 10-20 → 50%.
Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C227.6 A182 A159.3 A113.8 A102.4 A
30°C205 A164 A143.5 A102.5 A92.3 A
40°C180.4 A144.3 A126.3 A90.2 A81.2 A
50°C153.8 A123 A107.6 A76.9 A69.2 A

NEC 2023Every property and drop figure below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Properties

Circular mils250,000
DC resistance0.0847 Ω per 1000 ft
Ampacity at 75°C205 A
Overcurrent ceilingSet by ampacity
Largest standard breaker200 A
Area, THHN / THWN-20.397 in²
Area, XHHW-20.3904 in²
Area, THW0.4596 in²

Voltage drop over distance

Single-phase 240 V, carrying 205 A on 250 kcmil aluminum.

Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.
One-way distanceDropWithin 3%?
25 ft0.36%Yes
50 ft0.72%Yes
100 ft1.45%Yes
150 ft2.17%Yes
200 ft2.90%Yes
300 ft4.35%No

FAQ

Frequently asked questions

How many amps can 250 kcmil aluminum wire carry?

205 A at a 75°C termination rating under 2023 NEC Table 310.16, at the table's basis conditions of a 30°C ambient and no more than three current-carrying conductors. The 60°C column reads 170 A and the 90°C column 230 A, but terminations on breakers and equipment usually hold the practical answer to the 75°C column.

What size breaker goes with 250 kcmil aluminum wire?

200 A is the largest standard rating at or below the 205 A this conductor is good for at 75°C under the 2023 NEC. A hotter location or a fuller raceway derates the conductor and can push the breaker down; the derating table above shows how far.

Does 250 kcmil aluminum ampacity change with heat or bundling?

Yes. The published 205 A assumes a 30°C ambient and at most three current-carrying conductors in the raceway or cable. At a 40°C ambient with seven current-carrying conductors, the same 250 kcmil aluminum conductor is usable at 126.3 A after the 2023 NEC correction and adjustment factors. The derating table above covers more combinations.

How far can 250 kcmil aluminum wire run before voltage drop is a problem?

Carrying its full 205 A on a 240 V single-phase circuit, the circular-mil estimate this page uses stays inside a 3% drop out to about 207 ft one way, and reads 0.36% at 25 ft. Lighter loads drop proportionally less. The 2023 NEC treats 3% as a recommendation for efficient operation, not a general requirement.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).