Reference tables · Aluminum ampacity

2023 NEC · Table 310.16

1750 kcmil aluminum wire ampacity

At a 75°C termination rating, 1750 kcmil aluminum carries 545 A under the published table's basis conditions - 30°C ambient, no more than three current-carrying conductors.

1750 kcmil1,750,000 cmil

NEC 2023Every ampacity below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Ampacity by temperature rating

1750 kcmil aluminum, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.
Temperature ratingAmpacityTypical insulation
60°C455 A-
75°C545 ATHW
90°C615 ATHHN / THWN-2, XHHW-2

What 1750 kcmil aluminum is used for

1750 kcmil aluminum carries 545 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 500 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 545 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

NEC 2023Every derated value in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

1750 kcmil aluminum at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4-6 → 80%, 7-9 → 70%, 10-20 → 50%.
Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C605 A484 A423.5 A302.5 A272.2 A
30°C545 A436 A381.5 A272.5 A245.3 A
40°C479.6 A383.7 A335.7 A239.8 A215.8 A
50°C408.8 A327 A286.1 A204.4 A183.9 A

NEC 2023Every property and drop figure below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Properties

Circular mils1,750,000
DC resistance0.0121 Ω per 1000 ft
Ampacity at 75°C545 A
Overcurrent ceilingSet by ampacity
Largest standard breaker500 A
Area, THHN / THWN-2Not listed at this size
Area, XHHW-22.3127 in²
Area, THW2.4773 in²

Voltage drop over distance

Single-phase 240 V, carrying 545 A on 1750 kcmil aluminum.

Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.
One-way distanceDropWithin 3%?
25 ft0.14%Yes
50 ft0.28%Yes
100 ft0.55%Yes
150 ft0.83%Yes
200 ft1.10%Yes
300 ft1.65%Yes

FAQ

Frequently asked questions

How many amps can 1750 kcmil aluminum wire carry?

545 A at a 75°C termination rating under 2023 NEC Table 310.16, at the table's basis conditions of a 30°C ambient and no more than three current-carrying conductors. The 60°C column reads 455 A and the 90°C column 615 A, but terminations on breakers and equipment usually hold the practical answer to the 75°C column.

What size breaker goes with 1750 kcmil aluminum wire?

500 A is the largest standard rating at or below the 545 A this conductor is good for at 75°C under the 2023 NEC. A hotter location or a fuller raceway derates the conductor and can push the breaker down; the derating table above shows how far.

Does 1750 kcmil aluminum ampacity change with heat or bundling?

Yes. The published 545 A assumes a 30°C ambient and at most three current-carrying conductors in the raceway or cable. At a 40°C ambient with seven current-carrying conductors, the same 1750 kcmil aluminum conductor is usable at 335.7 A after the 2023 NEC correction and adjustment factors. The derating table above covers more combinations.

How far can 1750 kcmil aluminum wire run before voltage drop is a problem?

Carrying its full 545 A on a 240 V single-phase circuit, the circular-mil estimate this page uses stays inside a 3% drop out to about 545 ft one way, and reads 0.14% at 25 ft. Lighter loads drop proportionally less. The 2023 NEC treats 3% as a recommendation for efficient operation, not a general requirement.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).

Related

Nearby conductors