3-1/2" RMC has an internal area of 10.01 in². At the 40% limit that applies to more than two conductors, it holds up to 301 12 AWG THHN conductors.
Capacity
Maximum conductors by size and insulation
NEC 2023Every count in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
Maximum number of same-size, same-insulation conductors in 3-1/2" RMC (10.01 in² internal). Counts above two use the 40% limit; a dash means not even one fits, or the published area table does not list that insulation at that size.
Conductor
THHN / THWN-2
XHHW-2
THW
14 AWG
400
288
191
12 AWG
301
221
154
10 AWG
189
164
120
8 AWG
109
91
72
6 AWG
78
67
55
4 AWG
48
49
41
3 AWG
41
41
35
2 AWG
34
34
30
1 AWG
25
26
21
1/0 AWG
21
21
18
2/0 AWG
18
18
15
3/0 AWG
14
15
12
4/0 AWG
12
12
10
250 kcmil
10
10
8
300 kcmil
8
8
7
350 kcmil
7
7
6
400 kcmil
6
6
6
500 kcmil
5
5
5
600 kcmil
4
4
4
700 kcmil
4
4
3
750 kcmil
3
3
3
800 kcmil
3
3
3
900 kcmil
3
3
2
1000 kcmil
2
2
2
1250 kcmil
-
1
1
1500 kcmil
-
1
1
1750 kcmil
-
1
1
2000 kcmil
-
1
1
Fill limits
NEC 2023Every area and limit below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
Internal area
10.01 in²
One conductor
53% - 5.3053 in²
Two conductors
31% - 3.1031 in²
More than two
40% - 4.0040 in²
Fitting is not the same as finishing
These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.
Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count - the conduit fill calculator handles that.
Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry - see the bundling adjustment table.
Source:NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).