3" RMC has an internal area of 7.499 in². At the 40% limit that applies to more than two conductors, it holds up to 225 12 AWG THHN conductors.
Capacity
Maximum conductors by size and insulation
NEC 2023Every count in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
Maximum number of same-size, same-insulation conductors in 3" RMC (7.499 in² internal). Counts above two use the 40% limit; a dash means not even one fits, or the published area table does not list that insulation at that size.
Conductor
THHN / THWN-2
XHHW-2
THW
14 AWG
309
215
143
12 AWG
225
165
115
10 AWG
142
123
90
8 AWG
81
68
53
6 AWG
59
50
41
4 AWG
36
36
30
3 AWG
30
31
26
2 AWG
25
26
22
1 AWG
19
19
15
1/0 AWG
16
16
13
2/0 AWG
13
13
11
3/0 AWG
11
11
9
4/0 AWG
9
9
8
250 kcmil
7
7
6
300 kcmil
6
6
5
350 kcmil
5
5
5
400 kcmil
5
5
4
500 kcmil
4
4
3
600 kcmil
3
3
3
700 kcmil
3
3
2
750 kcmil
2
2
1
800 kcmil
2
2
1
900 kcmil
1
1
1
1000 kcmil
1
1
1
1250 kcmil
-
1
1
1500 kcmil
-
1
1
1750 kcmil
-
1
1
2000 kcmil
-
1
1
Fill limits
NEC 2023Every area and limit below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
Internal area
7.499 in²
One conductor
53% - 3.9745 in²
Two conductors
31% - 2.3247 in²
More than two
40% - 2.9996 in²
Fitting is not the same as finishing
These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.
Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count - the conduit fill calculator handles that.
Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry - see the bundling adjustment table.
Source:NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).