Reference tables · Conduit fill

PVC Schedule 40

2-1/2" PVC Sch 40 conduit fill capacity

2-1/2" PVC Sch 40 has an internal area of 4.695 in². At the 40% limit that applies to more than two conductors, it holds up to 141 12 AWG THHN conductors.

Capacity

Maximum conductors by size and insulation

NEC 2023Every count in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Maximum number of same-size, same-insulation conductors in 2-1/2" PVC Sch 40 (4.695 in² internal). Counts above two use the 40% limit; a dash means not even one fits, or the published area table does not list that insulation at that size.
ConductorTHHN / THWN-2XHHW-2THW
14 AWG19313589
12 AWG14110372
10 AWG897756
8 AWG514233
6 AWG373125
4 AWG222319
3 AWG191916
2 AWG161614
1 AWG12129
1/0 AWG10108
2/0 AWG887
3/0 AWG776
4/0 AWG555
250 kcmil444
300 kcmil443
350 kcmil333
400 kcmil332
500 kcmil221
600 kcmil111
700 kcmil111
750 kcmil111
800 kcmil111
900 kcmil111
1000 kcmil111
1250 kcmil-11
1500 kcmil-11
1750 kcmil-11

Fill limits

NEC 2023Every area and limit below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Internal area4.695 in²
One conductor53% - 2.4884 in²
Two conductors31% - 1.4555 in²
More than two40% - 1.8780 in²

Fitting is not the same as finishing

These counts are the mathematical fill limit, not a promise the pull will go well. A raceway at 39% fill with four 90° bends and a hundred feet between pull points is legal and miserable. Experienced installers routinely size up a trade size on long or bendy runs, and the material cost difference is usually smaller than the labour cost of a fight.

Two other things this table does not model. Nipples 24 inches and shorter between enclosures are permitted a much higher fill. And a mixed set of conductor sizes has to be summed by area rather than looked up by count - the conduit fill calculator handles that.

Remember also that conductor count drives ampacity derating separately. Filling this conduit with current-carrying conductors will reduce what each one can carry - see the bundling adjustment table.

Source: NFPA 70, National Electrical Code, Chapter 9, Table 1; NFPA 70, National Electrical Code, Chapter 9, Table 4; NFPA 70, National Electrical Code, Chapter 9, Table 5. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).