Reference tables · Copper ampacity

2023 NEC · Table 310.16

14 AWG copper wire ampacity

At a 75°C termination rating, 14 AWG copper carries 20 A under the published table's basis conditions - 30°C ambient, no more than three current-carrying conductors. Overcurrent protection is separately capped at 15 A by the small-conductor rule.

14 AWG4,110 cmil

NEC 2023Every ampacity below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Ampacity by temperature rating

14 AWG copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.
Temperature ratingAmpacityTypical insulation
60°C15 A-
75°C20 ATHW
90°C25 ATHHN / THWN-2, XHHW-2

What 14 AWG copper is used for

14 AWG copper is the smallest conductor in general branch-circuit use, and it is a 15 A conductor in practice. It is what most residential lighting circuits are wired in, and the reason a 15 A breaker is the smallest standard rating.

Note the gap between the table and the ceiling. The 90°C column reads 25 A, but a 14 AWG copper conductor cannot be protected above 15 A regardless - the small-conductor rule sets that ceiling independently of ampacity. The higher table value exists so the conductor has headroom to be derated from, not so it can be put on a larger breaker.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 20 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

NEC 2023Every derated value in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

14 AWG copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4-6 → 80%, 7-9 → 70%, 10-20 → 50%.
Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C15 A15 A15 A11.1 A10 A
30°C15 A15 A14 A10 A9 A
40°C15 A14.1 A12.3 A8.8 A7.9 A
50°C15 A12 A10.5 A7.5 A6.8 A

NEC 2023Every property and drop figure below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Properties

Circular mils4,110
DC resistance3.14 Ω per 1000 ft
Ampacity at 75°C20 A
Overcurrent ceiling15 A (small-conductor rule)
Largest standard breaker15 A
Area, THHN / THWN-20.0097 in²
Area, XHHW-20.0139 in²
Area, THW0.0209 in²

Voltage drop over distance

Single-phase 240 V, carrying 15 A on 14 AWG copper.

Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.
One-way distanceDropWithin 3%?
25 ft0.98%Yes
50 ft1.96%Yes
100 ft3.92%No
150 ft5.89%No
200 ft7.85%No
300 ft11.77%No

FAQ

Frequently asked questions

How many amps can 14 AWG copper wire carry?

20 A at a 75°C termination rating under 2023 NEC Table 310.16, at the table's basis conditions of a 30°C ambient and no more than three current-carrying conductors. The 60°C column reads 15 A and the 90°C column 25 A, but terminations on breakers and equipment usually hold the practical answer to the 75°C column. Overcurrent protection for 14 AWG copper is separately capped at 15 A by the small-conductor rule.

What size breaker goes with 14 AWG copper wire?

15 A. The 75°C column of 2023 NEC Table 310.16 puts 14 AWG copper at 20 A, but the small-conductor rule (2023 NEC 240.4(D)) separately caps its overcurrent protection at 15 A, and 15 A is the largest standard rating at or below that ceiling. A hotter location or a fuller raceway derates the conductor and can push the breaker down; the derating table above shows how far.

Does 14 AWG copper ampacity change with heat or bundling?

Yes. The published 20 A assumes a 30°C ambient and at most three current-carrying conductors in the raceway or cable. At a 40°C ambient with seven current-carrying conductors, the same 14 AWG copper conductor is usable at 12.3 A after the 2023 NEC correction and adjustment factors. The derating table above covers more combinations.

How far can 14 AWG copper wire run before voltage drop is a problem?

Carrying its full 15 A on a 240 V single-phase circuit, the circular-mil estimate this page uses stays inside a 3% drop out to about 76 ft one way, and reads 0.98% at 25 ft. Lighter loads drop proportionally less. The 2023 NEC treats 3% as a recommendation for efficient operation, not a general requirement.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).