Ampacity by temperature rating
| Temperature rating | Ampacity | Typical insulation |
|---|---|---|
| 60°C | 20 A | - |
| 75°C | 25 A | THW |
| 90°C | 30 A | THHN / THWN-2, XHHW-2 |
Reference tables · Copper ampacity
2023 NEC · Table 310.16
At a 75°C termination rating, 12 AWG copper carries 25 A under the published table's basis conditions - 30°C ambient, no more than three current-carrying conductors. Overcurrent protection is separately capped at 20 A by the small-conductor rule.
NEC 2023Every ampacity below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
| Temperature rating | Ampacity | Typical insulation |
|---|---|---|
| 60°C | 20 A | - |
| 75°C | 25 A | THW |
| 90°C | 30 A | THHN / THWN-2, XHHW-2 |
12 AWG copper is the workhorse of 20 A branch circuits - receptacles, kitchen small-appliance circuits, and general-purpose power. It pairs with a 20 A breaker and is the smallest conductor most jurisdictions accept for receptacle circuits in a kitchen or garage.
Note the gap between the table and the ceiling. The 90°C column reads 30 A, but a 12 AWG copper conductor cannot be protected above 20 A regardless - the small-conductor rule sets that ceiling independently of ampacity. The higher table value exists so the conductor has headroom to be derated from, not so it can be put on a larger breaker.
Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 25 A column at the terminals. Check the equipment's listing rather than assuming.
Derating
NEC 2023Every derated value in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
| Ambient | 3 conductors | 4 conductors | 7 conductors | 10 conductors | 21 conductors |
|---|---|---|---|---|---|
| 20°C | 20 A | 20 A | 19.4 A | 13.9 A | 12.5 A |
| 30°C | 20 A | 20 A | 17.5 A | 12.5 A | 11.3 A |
| 40°C | 20 A | 17.6 A | 15.4 A | 11 A | 9.9 A |
| 50°C | 18.8 A | 15 A | 13.1 A | 9.4 A | 8.4 A |
NEC 2023Every property and drop figure below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
| Circular mils | 6,530 |
|---|---|
| DC resistance | 1.98 Ω per 1000 ft |
| Ampacity at 75°C | 25 A |
| Overcurrent ceiling | 20 A (small-conductor rule) |
| Largest standard breaker | 20 A |
| Area, THHN / THWN-2 | 0.0133 in² |
| Area, XHHW-2 | 0.0181 in² |
| Area, THW | 0.026 in² |
Single-phase 240 V, carrying 20 A on 12 AWG copper.
| One-way distance | Drop | Within 3%? |
|---|---|---|
| 25 ft | 0.82% | Yes |
| 50 ft | 1.65% | Yes |
| 100 ft | 3.29% | No |
| 150 ft | 4.94% | No |
| 200 ft | 6.58% | No |
| 300 ft | 9.88% | No |
FAQ
25 A at a 75°C termination rating under 2023 NEC Table 310.16, at the table's basis conditions of a 30°C ambient and no more than three current-carrying conductors. The 60°C column reads 20 A and the 90°C column 30 A, but terminations on breakers and equipment usually hold the practical answer to the 75°C column. Overcurrent protection for 12 AWG copper is separately capped at 20 A by the small-conductor rule.
20 A. The 75°C column of 2023 NEC Table 310.16 puts 12 AWG copper at 25 A, but the small-conductor rule (2023 NEC 240.4(D)) separately caps its overcurrent protection at 20 A, and 20 A is the largest standard rating at or below that ceiling. A hotter location or a fuller raceway derates the conductor and can push the breaker down; the derating table above shows how far.
Yes. The published 25 A assumes a 30°C ambient and at most three current-carrying conductors in the raceway or cable. At a 40°C ambient with seven current-carrying conductors, the same 12 AWG copper conductor is usable at 15.4 A after the 2023 NEC correction and adjustment factors. The derating table above covers more combinations.
Carrying its full 20 A on a 240 V single-phase circuit, the circular-mil estimate this page uses stays inside a 3% drop out to about 91 ft one way, and reads 0.82% at 25 ft. Lighter loads drop proportionally less. The 2023 NEC treats 3% as a recommendation for efficient operation, not a general requirement.
Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).