Reference tables · Copper ampacity

2023 NEC · Table 310.16

300 kcmil copper wire ampacity

At a 75°C termination rating, 300 kcmil copper carries 285 A under the published table's basis conditions - 30°C ambient, no more than three current-carrying conductors.

300 kcmil300,000 cmil

NEC 2023Every ampacity below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Ampacity by temperature rating

300 kcmil copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.
Temperature ratingAmpacityTypical insulation
60°C240 A-
75°C285 ATHW
90°C320 ATHHN / THWN-2, XHHW-2

What 300 kcmil copper is used for

300 kcmil copper carries 285 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 250 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 285 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

NEC 2023Every derated value in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

300 kcmil copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4-6 → 80%, 7-9 → 70%, 10-20 → 50%.
Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C316.4 A253.1 A221.4 A158.2 A142.4 A
30°C285 A228 A199.5 A142.5 A128.3 A
40°C250.8 A200.6 A175.6 A125.4 A112.9 A
50°C213.8 A171 A149.6 A106.9 A96.2 A

NEC 2023Every property and drop figure below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Properties

Circular mils300,000
DC resistance0.0429 Ω per 1000 ft
Ampacity at 75°C285 A
Overcurrent ceilingSet by ampacity
Largest standard breaker250 A
Area, THHN / THWN-20.4608 in²
Area, XHHW-20.4536 in²
Area, THW0.5281 in²

Voltage drop over distance

Single-phase 240 V, carrying 285 A on 300 kcmil copper.

Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.
One-way distanceDropWithin 3%?
25 ft0.26%Yes
50 ft0.51%Yes
100 ft1.02%Yes
150 ft1.53%Yes
200 ft2.04%Yes
300 ft3.06%No

FAQ

Frequently asked questions

How many amps can 300 kcmil copper wire carry?

285 A at a 75°C termination rating under 2023 NEC Table 310.16, at the table's basis conditions of a 30°C ambient and no more than three current-carrying conductors. The 60°C column reads 240 A and the 90°C column 320 A, but terminations on breakers and equipment usually hold the practical answer to the 75°C column.

What size breaker goes with 300 kcmil copper wire?

250 A is the largest standard rating at or below the 285 A this conductor is good for at 75°C under the 2023 NEC. A hotter location or a fuller raceway derates the conductor and can push the breaker down; the derating table above shows how far.

Does 300 kcmil copper ampacity change with heat or bundling?

Yes. The published 285 A assumes a 30°C ambient and at most three current-carrying conductors in the raceway or cable. At a 40°C ambient with seven current-carrying conductors, the same 300 kcmil copper conductor is usable at 175.6 A after the 2023 NEC correction and adjustment factors. The derating table above covers more combinations.

How far can 300 kcmil copper wire run before voltage drop is a problem?

Carrying its full 285 A on a 240 V single-phase circuit, the circular-mil estimate this page uses stays inside a 3% drop out to about 293 ft one way, and reads 0.26% at 25 ft. Lighter loads drop proportionally less. The 2023 NEC treats 3% as a recommendation for efficient operation, not a general requirement.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).

Related

Nearby conductors