Reference tables · Copper ampacity

2023 NEC · Table 310.16

3/0 AWG copper wire ampacity

At a 75°C termination rating, 3/0 AWG copper carries 200 A under the published table's basis conditions - 30°C ambient, no more than three current-carrying conductors.

3/0 AWG167,800 cmil

NEC 2023Every ampacity below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Ampacity by temperature rating

3/0 AWG copper, at a 30°C ambient with no more than three current-carrying conductors in a raceway or cable. The 90°C column is normally used only as the starting point for derating.
Temperature ratingAmpacityTypical insulation
60°C165 A-
75°C200 ATHW
90°C225 ATHHN / THWN-2, XHHW-2

What 3/0 AWG copper is used for

3/0 AWG copper carries 200 A at 75°C. Conductors this size are service entrance and main feeder conductors - the run between a meter and a panel, or between a main panel and a large subpanel. It pairs with a 200 A overcurrent device.

Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 200 A column at the terminals. Check the equipment's listing rather than assuming.

Derating

Ampacity in real conditions

NEC 2023Every derated value in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

3/0 AWG copper at a 75°C termination rating, corrected for ambient temperature and adjusted for the number of current-carrying conductors, then capped by any small-conductor limit. Adjustment factors: 4-6 → 80%, 7-9 → 70%, 10-20 → 50%.
Ambient3 conductors4 conductors7 conductors10 conductors21 conductors
20°C222 A177.6 A155.4 A111 A99.9 A
30°C200 A160 A140 A100 A90 A
40°C176 A140.8 A123.2 A88 A79.2 A
50°C150 A120 A105 A75 A67.5 A

NEC 2023Every property and drop figure below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.

Properties

Circular mils167,800
DC resistance0.0766 Ω per 1000 ft
Ampacity at 75°C200 A
Overcurrent ceilingSet by ampacity
Largest standard breaker200 A
Area, THHN / THWN-20.2679 in²
Area, XHHW-20.2642 in²
Area, THW0.3117 in²

Voltage drop over distance

Single-phase 240 V, carrying 200 A on 3/0 AWG copper.

Circular-mil estimate at full load. Lighter loads drop proportionally less. Use the voltage drop calculator for your actual current.
One-way distanceDropWithin 3%?
25 ft0.32%Yes
50 ft0.64%Yes
100 ft1.28%Yes
150 ft1.92%Yes
200 ft2.56%Yes
300 ft3.84%No

FAQ

Frequently asked questions

How many amps can 3/0 AWG copper wire carry?

200 A at a 75°C termination rating under 2023 NEC Table 310.16, at the table's basis conditions of a 30°C ambient and no more than three current-carrying conductors. The 60°C column reads 165 A and the 90°C column 225 A, but terminations on breakers and equipment usually hold the practical answer to the 75°C column.

What size breaker goes with 3/0 AWG copper wire?

200 A is the largest standard rating at or below the 200 A this conductor is good for at 75°C under the 2023 NEC. A hotter location or a fuller raceway derates the conductor and can push the breaker down; the derating table above shows how far.

Does 3/0 AWG copper ampacity change with heat or bundling?

Yes. The published 200 A assumes a 30°C ambient and at most three current-carrying conductors in the raceway or cable. At a 40°C ambient with seven current-carrying conductors, the same 3/0 AWG copper conductor is usable at 123.2 A after the 2023 NEC correction and adjustment factors. The derating table above covers more combinations.

How far can 3/0 AWG copper wire run before voltage drop is a problem?

Carrying its full 200 A on a 240 V single-phase circuit, the circular-mil estimate this page uses stays inside a 3% drop out to about 234 ft one way, and reads 0.32% at 25 ft. Lighter loads drop proportionally less. The 2023 NEC treats 3% as a recommendation for efficient operation, not a general requirement.

Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).