Ampacity by temperature rating
| Temperature rating | Ampacity | Typical insulation |
|---|---|---|
| 60°C | 525 A | - |
| 75°C | 625 A | THW |
| 90°C | 705 A | THHN / THWN-2, XHHW-2 |
Reference tables · Copper ampacity
2023 NEC · Table 310.16
At a 75°C termination rating, 1500 kcmil copper carries 625 A under the published table's basis conditions - 30°C ambient, no more than three current-carrying conductors.
NEC 2023Every ampacity below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
| Temperature rating | Ampacity | Typical insulation |
|---|---|---|
| 60°C | 525 A | - |
| 75°C | 625 A | THW |
| 90°C | 705 A | THHN / THWN-2, XHHW-2 |
1500 kcmil copper carries 625 A at 75°C. Conductors in the kcmil range are service, feeder, and distribution conductors, frequently run as paralleled sets under rules this reference does not model. It pairs with a 600 A overcurrent device.
Terminations usually decide the practical answer. Breakers and equipment are typically listed for 60°C or 75°C, so even 90°C-rated insulation on this conductor is normally limited to the 625 A column at the terminals. Check the equipment's listing rather than assuming.
Derating
NEC 2023Every derated value in this table is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
| Ambient | 3 conductors | 4 conductors | 7 conductors | 10 conductors | 21 conductors |
|---|---|---|---|---|---|
| 20°C | 693.8 A | 555 A | 485.6 A | 346.9 A | 312.2 A |
| 30°C | 625 A | 500 A | 437.5 A | 312.5 A | 281.3 A |
| 40°C | 550 A | 440 A | 385 A | 275 A | 247.5 A |
| 50°C | 468.8 A | 375 A | 328.1 A | 234.4 A | 210.9 A |
NEC 2023Every property and drop figure below is transcribed from the 2023 NEC (NFPA 70, 2023). The code is republished on a three-year cycle and adoption varies by jurisdiction - confirm against your locally adopted edition and your authority having jurisdiction (AHJ) before you build.
| Circular mils | 1,500,000 |
|---|---|
| DC resistance | 0.00858 Ω per 1000 ft |
| Ampacity at 75°C | 625 A |
| Overcurrent ceiling | Set by ampacity |
| Largest standard breaker | 600 A |
| Area, THHN / THWN-2 | Not listed at this size |
| Area, XHHW-2 | 2.0156 in² |
| Area, THW | 2.1695 in² |
Single-phase 240 V, carrying 625 A on 1500 kcmil copper.
| One-way distance | Drop | Within 3%? |
|---|---|---|
| 25 ft | 0.11% | Yes |
| 50 ft | 0.22% | Yes |
| 100 ft | 0.45% | Yes |
| 150 ft | 0.67% | Yes |
| 200 ft | 0.90% | Yes |
| 300 ft | 1.34% | Yes |
FAQ
625 A at a 75°C termination rating under 2023 NEC Table 310.16, at the table's basis conditions of a 30°C ambient and no more than three current-carrying conductors. The 60°C column reads 525 A and the 90°C column 705 A, but terminations on breakers and equipment usually hold the practical answer to the 75°C column.
600 A is the largest standard rating at or below the 625 A this conductor is good for at 75°C under the 2023 NEC. A hotter location or a fuller raceway derates the conductor and can push the breaker down; the derating table above shows how far.
Yes. The published 625 A assumes a 30°C ambient and at most three current-carrying conductors in the raceway or cable. At a 40°C ambient with seven current-carrying conductors, the same 1500 kcmil copper conductor is usable at 385 A after the 2023 NEC correction and adjustment factors. The derating table above covers more combinations.
Carrying its full 625 A on a 240 V single-phase circuit, the circular-mil estimate this page uses stays inside a 3% drop out to about 669 ft one way, and reads 0.11% at 25 ft. Lighter loads drop proportionally less. The 2023 NEC treats 3% as a recommendation for efficient operation, not a general requirement.
Source: NFPA 70, National Electrical Code, Table 310.16; NFPA 70, National Electrical Code, Table 310.15(B)(1)(1); NFPA 70, National Electrical Code, Table 310.15(C)(1); NFPA 70, National Electrical Code, Chapter 9, Table 8. Published by NFPA.NEC 2023Transcribed from the 2023 NEC (NFPA 70, 2023). Confirm against your locally adopted edition and your authority having jurisdiction (AHJ).
Related